Three-level modular design, bidirectional energy conversion
Each module operates independently, and the system online rate is 99%;No quick-wear parts, modular N + 1 redundancy
Active / reactive four-quadrant adjustment function;Deploy on demand and automatically operate locally during peak load shaving and valley filling
Support the linkage with the BMS and EMS;This system offers multiple protection
Rated AC Power
50kVA |
Mode of Connection
Three-phase and four-wire |
AC Overload Capacity
55kVA |
Allowable Grid Voltage
380/400(-15%~15%)Vac |
Allowable Grid Frequency
50/60(-2.5~2.5)Hz |
Total Current Harmonic Distortion Rat
≤3% |
Power Factor
0.99/-1~1 |
Maximum DC Power
55kw |
DC Voltage Range
500~850Vdc |
Number of DC Access Channels
1 |
Maximum Direct Current
110A |
Voltage Regulation Accuracy
≤±1% |
Current Regulation Accuracy
≤±1% |
Maximum Conversion Efficiency
97.3% |
Dimensions(width×height×depth)
800×2160×800 mm |
Weight
465kg |
Noise
<75dB |
Protection Level
IP20 |
Allowable Ambient Temperature
-20~60℃(More than 50 ℃ derating) |
Cooling Mode
Air cooling |
Allowable Relative Humidity
0~95%(No condensation) |
Altitude
3000m(More than 3000m derating) |
Communication Interface
RS 485,Ethernet,CAN |
Communication Protocol
ModbusTCP/RTU,IEC104 |
BMS Access
Support |
Rated AC Power
100kVA |
Mode of Connection
Three-phase and four-wire |
AC Overload Capacity
110kVA |
Allowable Grid Voltage
380/400(-15%~15%)Vac |
Allowable Grid Frequency
50/60(-2.5~2.5)Hz |
Total Current Harmonic Distortion Rat
≤3% |
Power Factor
0.99/-1~1 |
Maximum DC Power
110kw |
DC Voltage Range
500~850Vdc |
Number of DC Access Channels
1 |
Maximum Direct Current
220A |
Voltage Regulation Accuracy
≤±1% |
Current Regulation Accuracy
≤±1% |
Maximum Conversion Efficiency
97.3% |
Dimensions(width×height×depth)
800×2160×800 mm |
Weight
680kg |
Noise
<75dB |
Protection Level
IP20 |
Allowable Ambient Temperature
-20~60℃(More than 50 ℃ derating) |
Cooling Mode
Air cooling |
Allowable Relative Humidity
0~95%(No condensation) |
Altitude
3000m(More than 3000m derating) |
Communication Interface
RS 485,Ethernet,CAN |
Communication Protocol
ModbusTCP/RTU,IEC104 |
BMS Access
Support |
Rated AC Power
150kVA |
Mode of Connection
Three-phase and four-wire |
AC Overload Capacity
165kVA |
Allowable Grid Voltage
380/400(-15%~15%)Vac |
Allowable Grid Frequency
50/60(-2.5~2.5)Hz |
Total Current Harmonic Distortion Rat
≤3% |
Power Factor
0.99/-1~1 |
Maximum DC Power
165kw |
DC Voltage Range
500~850Vdc |
Number of DC Access Channels
1 |
Maximum Direct Current
330A |
Voltage Regulation Accuracy
≤±1% |
Current Regulation Accuracy
≤±1% |
Maximum Conversion Efficiency
97.3% |
Dimensions(width×height×depth)
800×2160×800 mm |
Weight
910kg |
Noise
<75dB |
Protection Level
IP20 |
Allowable Ambient Temperature
-20~60℃(More than 50 ℃ derating) |
Cooling Mode
Air cooling |
Allowable Relative Humidity
0~95%(No condensation) |
Altitude
3000m(More than 3000m derating) |
Communication Interface
RS 485,Ethernet,CAN |
Communication Protocol
ModbusTCP/RTU,IEC104 |
BMS Access
Support |